Battery Backup Calculator (UPS / Inverter)
Find the battery Ah and kWh needed for your load and backup hours.
Loading calculatorβ¦
Worked example
Example: a 500 W load for 4 hours on a 24 V lead-acid bank with a 90% efficient inverter.
| Capacity needed | 185 Ah at 24 V |
|---|---|
| Energy storage | 4.44 kWh |
How the Battery Backup Calculator (UPS / Inverter) works
Enter load, backup hours, battery voltage and type. The calculator returns the battery capacity needed in Ah and kWh.
Formula: Ah = (Load W Γ Hours) Γ· (Efficiency Γ Usable % Γ Voltage)
What to know before you calculate
Lead-acid batteries should only be discharged to about 50% for a long life, while lithium (LiFePO4) can be used to roughly 80%, which is why the same load needs a bigger lead-acid bank.
The calculation
Battery energy is simple: the load in watts multiplied by the hours you want it to run gives watt-hours. Two real-world factors then increase the size you need. The inverter wastes some energy as heat, usually 10 to 15%, and a battery should not be emptied completely. Lead-acid and tubular batteries are normally used to about 50% of their rated capacity to keep them healthy; lithium iron phosphate can use around 80%.
Divide the final watt-hours by the battery bank voltage to get amp-hours (Ah). A 12 V battery rated 150 Ah stores about 1.8 kWh in total, but only about 0.9 kWh of that is usable at 50% depth of discharge.
Series and parallel
Connecting batteries in series adds their voltage, and connecting them in parallel adds their capacity. Match your inverter's DC input: a 24 V inverter needs two 12 V batteries in series, and a second pair in parallel doubles the capacity. Always connect identical batteries of the same age and brand.
Choosing the load
For a normal load-shedding setup, add up only what you actually want during an outage, such as fans, lights, a router and a refrigerator, rather than the whole house. A refrigerator and a ceiling fan together use far less than an air conditioner, which will drain a battery bank within an hour or two. If the load includes an AC or a water pump, use the battery result together with the inverter surge rating.
Lead-acid or lithium
Lead-acid batteries cost less to buy, but they are heavy, need maintenance and wear out faster when often discharged deeply. Lithium costs more up front, allows deeper use and lasts for more cycles. Compare the cost per usable kilowatt-hour over the battery's warranted life instead of the sticker price alone.
Tips for accurate results
Use the load that will really run during an outage. The calculator already allows for inverter efficiency and usable battery capacity. Motor loads such as ACs and pumps still need extra inverter capacity at start-up.
Roman Urdu mein
Load-shedding mein chalne wala load (watts) aur backup ke ghantay daalein to battery ki capacity (Ah aur kWh) ka andaza mil jata hai. Lead-acid aur lithium ki usable capacity mukhtalif hoti hai.
Frequently asked questions
How long will a battery last on my load?
Backup hours = Usable battery Wh Γ inverter efficiency Γ· load watts.
Does this allow for battery ageing?
No. Batteries lose capacity over the years, so installers often add a margin. Ask for the warranty and the cycle life of the battery you are offered.
More calculators
Disclaimer: results are estimates for general information. Confirm figures with the official authority, bank, institution or a qualified professional.